HVA - Mini Circuit Breaker(MCB)

 

Specifications:

Standard Conformity IS 8828:96 & IEC(60898:2002)
Type/Series B C D
Rated Current(In) A 6 - 40 0.5 - 63 0.5 - 63
Rated Voltage(ac)(Ue) V 240/415 240/415 240/415
Rated Frequency(f) Hz 50 50 50
Poles   1P.2P.3P.4P   2P.2P3P.4P
Rated Short Circuit Breaking Capacity kA 10 10 4.5
Magnetic Release Setting   (3 - 5)In (5-10)In (10-20) In
Rated Insulation Voltage(ui) V 660 660 660
Reted Impulse Voltage(Uimp) kV 4 4 4
Electrical/Mechanical Endurance
(no.of operations)
less than 32A
More than 32A
 

20,000
10,000


20,000
10,000


20,000
10,000
Ambient Temperature () -5 to +55 -5 to +55 -5 to +55
Terminal Capacity(max) sq.mm 25 25 25
Vibration g 3 3 3
Shock   40mm free fall 40mm free fall 40mm free fall
PRotection Class     IP - 20  
Installation Position     Vertical / Horizontal  
Mounting     Clip on DIN Rail (35mm 7.5 mm)  
Case & Cover     Moulded,flame retardant thermoplastic material  

Characteristics curve:
Thermal Tripping Magnetic Tripping
As per No tripping Tripping Time Hold Trip Time
IS:8828:96 current current Limits current current Limits
  1 1 t 1 1 t
B Curve 1.131N   1h 31N   Y0.1s
    1.451N 1h   51N 0.1s
C Cure 1.131N   1h 51N   Y0.1s
    1.451N 1h   101N 0.1s
D Cure 1.131N   1h 101N   0.1s
    1.451N 1h   201N 0.1s
13=2.551N 1st60s for 1N32A
1st120s for 1N32A

Tripping Characteristics:
Based on theTripping Characteristics,MCBs are available in?'B','C'  and 'D' curve to suit different types of applications.
'B' Curve:for protection of electrical circuits with equipment that does not cause surge current (lighting and distribution circuits) Short circuit release is set to (3-5) In
'C' Curve:for protection of electrical circuits with equipment that causes surge current (inductive loads and motor circuits) Short circuit release is set to (5-10) In
'D' Curve: for protection of electrical circuits which causes high inrush current,typically 12-15 times the thermal rated current (transformers,X-ray machines etc.)Short circuit release is set to (10-20) In

 

Characteristics curve:
HVA Characteristics curve - Mini Circuit Breaker(MCB)

 

Dimensions:
HVA Dimensions - Mini Circuit Breaker(MCB)


Previous Page: SX